Amercable Arctic Grade CIR 2 AWG Type VFD Power Cable UL Listed as Type TC-ER & Type TC-ER-HL 3/C Gexol Ins.2kV Rated 90C 37-102-314

Amercable Arctic Grade CIR 2 AWG Type VFD Power Cable UL Listed as Type TC-ER & Type TC-ER-HL 3/C Gexol Ins.2kV Rated 90C 37-102-314

Select gauge from drop-down menu for prices:

Amercable Arctic Grade CIR 2 AWG Type VFD Power Cable UL Listed as Type TC-ER & Type TC-ER-HL 3/C Gexol Ins.2kV Rated 90C 37-102-314
Amercable Arctic Grade CIR 2 AWG Type VFD Power Cable UL Listed as Type TC-ER & Type TC-ER-HL 3/C Gexol Ins. 2kV Rated 90C 37-102-314

Power Conductors (x3): Soft annealed flexible stranded tinned copper per IEEE 1580 Table 11.

Ground Conductors (x3): Soft annealed flexible stranded tinned copper per IEEE 1580 Table 11. Gexol® insulation sized per UL 1277. Color: Green

Insulation (2kV): Gexol® cross-linked flame retardant polyolefin, meeting the requirements for Type P of IEEE 1580 and Type X110 of UL 1309/CSA 245. Color: Gray with printed phase I.D. (Black-Red-Blue)

Shield: Overall tinned copper braid plus aluminum/polyester tape providing 100% coverage.

Jacket: A black, flame retardant, oil, abrasion, chemical and sunlight resistant thermoset CPE meeting UL 1309/CSA 245 and IEEE 1580.

Safer to Handle: CIR® has no sharp metal armor edges that imperil worker’s hands during splicing and installation of connectors

CIR® Ratings & Approvals:
• 90°C temperature rating
• UL Listed as Marine Shipboard Cable (E111461)
• UL Listed as Type TC-ER
• UL Listed as TC-ER-HL (cables up to 1” in diameter)
• American Bureau of Shipping (ABS)
• Flame Retardant – IEEE 1202
• Suitable for use in Class I, Div 2 and Zone 2 environments
• Suitable for Class 1, Div 1 and Zone 1 environments. (cables less than 1” in OD)

Application: A flexible, braid and foil shielded, 2kV power cable specifically engineered for use in variable frequency AC motor drive (VFD) applications.

Features:
• Specially engineered cable design produces a longer cable life in VFD applications in severe cold environments.
• Exceeds CSA cold bend/cold impact (-40°C/-35°F)
• Brittlepoint as per ASTM D 7646-07 exceeds -65°C for Jacket and -75°C for insulation
• Overall braid and foil shield provides 100% coverage containing VFD EMI emissions.
• Symmetrical insulated ground conductors reduce induced voltage imbalances and carry common mode noise back to the drive.
• High strand count conductors and braid shield design is much more flexible, easier to install and more resistant to vibration than Type MC cable.
• Gexol’s lower dielectric constant (standard XLPEs,EPRs and other Type P insulation materials have higher dielectric constants) reduces reflected wave peak voltage magnitudes. This allows for longer output cable distances and minimizes the effect of high frequency noise induced into the plant ground system.
• 2kV insulation thickness resists the repetitive 2x voltage spikes from 600V VFDs and reduces drive over current trip problems due to cable charging current.
• Passes the same stringent crush and impact testing required by UL 2225 for Type MC-HL
• Gas & vapor tight – impervious to water and air
• Smaller bend radius (up to 40% smaller) than Type MC
• Considerably more flexible than Type MC
• Reduced installation time and cost comparedto Type MC
• Glands cost up to 50% less

technical specifications:
size awg/kcmil 2
nominal diameter inches* 1.341
weight per 1000 ft. 1276
dc resist.@ 25°c(ohms/1k ft) 0.184
ac resist.@ 90°c, 60 hz (ohms/1k ft) 0.230
inductive reactance (ohms/1k ft) 0.029
voltage drop@ 90°c (volts/amp/1k ft) 0.348
green insulated grounding size (awg) 10
ieee ampacity 90°c 111
nec ampacity 90°c 130
ieee ampacity 75°c 93
nec ampacity 90°c 115
amercable part number 37-102-314cirvfda