HW113 Thermcouple Extension Cable 600 Volt UL Type TC, 90°C Single and Multiple Pairs Individual and Overall Shield FR-XLP or FR-EP Insulation CPE Jacket Solid Alloy Conductors - 20 AWG - 4 Pairs - T X ANSI Type

HW113 Thermcouple Extension Cable 600 Volt UL Type TC, 90°C Single and Multiple Pairs Individual and Overall Shield FR-XLP or FR-EP Insulation CPE Jacket Solid Alloy Conductors - 20 AWG - 4 Pairs - T X ANSI Type

Select gauge from drop-down menu for prices:

HW113 Thermcouple Extension Cable 600 Volt UL Type TC, 90°C Single and Multiple Pairs Individual and Overall Shield FR-XLP or FR-EP Insulation CPE Jacket Solid Alloy Conductors - 20 AWG - 4 Pairs - T X ANSI Type

Product Details

Technical Specifications:
Catalog Number HW113 2004T
Size AWG 20
No. of Pairs 4
Insulation Thickness Mils 12
Jacket Thickness Mils 50
ANSI Type T X
Overall Diameter 0.42
Net Weight Lbs/Mft 95

Specifications:

  • HW113
  • Thermcouple Extension Cable
  • 600 Volt UL Type TC, 90°C
  • Single and Multiple Pairs
  • Individual and Overall Shield
  • FR-XLP or FR-EP Insulation
  • CPE Jacket
  • Solid Alloy Conductors

Application:
Superior flame-retardant cable for use in thermocouple extension applications in caustic environments where protection from electrostatic interference is required. UL listed as Type TC and approved for installation indoors or outdoors, aerially, in conduits, ducts and cable trays. May be installed at temperatures as low as -35°C and used in NEC Class 1, Division 2 hazardous locations.

Conductors:
Annealed, solid thermocouple extension-grade alloys calibrated to standard limits of error per ANSI-MC96.1.

Insulation:
Flame-retardant ethylene propylene rubber (FR-EP) color coded per ANSI-MC96.1. Flame-retardant cross-linked polyethylene per ICEA S-66-524.

Individual Shield:
Aluminum-polymer tape providing 100% coverage with a flexible 7-strand tinned copper drain wire.

Communication Wire:
Multipair constructions contain a 7-strand bare copper orange PVC-insulated communication wire.

Overall Shield:
Aluminum-polymer tape providing 100% coverage with a flexible 7-strand tinned copper drain wire.

Jacket:
Sunlight-resistant chlorinated polyethylene (CPE) color coded per ANSI-MC96.1. A ripcord is applied longitudinally under the jacket to facilitate stripping.

Flame Tests:

  • IEEE 383 70,000 BTU/hr flame test
  • IEEE 1202 70,000 BTU/hr
  • UL Standard 13 70,000 BTU/hr flame test
  • CSA FT4 flame test