General Cable Anaconda® Brand Type MP-GC (Uniblend EPR) Mine Power Feeder w/Ground Check EPR CPE 15000 Volts Three Conductor

General Cable Anaconda® Brand Type MP-GC (Uniblend EPR) Mine Power Feeder w/Ground Check EPR CPE 15000 Volts Three Conductor

Product Details

Type MP-GC 3 Conductor cable comes with three compacted Class B live copper conductors that are bare, stranded and annealed. The use of annealed copper conductors instead of standard stiff copper conductors affirms the flexibility of this cable. These copper conductors are shielded with ESS (extruded strand shield) and insulated with Ethylene Propylene Rubber (EPR) that is black color coded for easy identification. EPR insulation is double shielded with an extruded thermosetting semi-conducting layer. 

The assembly is wrapped with an overlapped copper annealed tape shield. This cable features a ground check conductor made of stranded Class B, annealed and coated copper conductors with a yellow propylene insulation for identification. Two grounding annealed copper conductors have different individual insulation from the live copper conductors. It is jacketed with a lead cured Chlorinated Polyethylene (CPE) compound for additional protection.

Standards and Approvals

1.C22 ICEA S-75-381 test for power feeders and portable cables
2.Flame test as per MSHA listed requirements
3.CSA.2 number 96.1 Mine Power Feeder Cable

Conductors
Three live copper conductor cable is also referred to as a three-phased power cable and can be deployed in three phase power distribution lines. It is made of flexible copper conductors that makes it easy to install. Flexible power cables can be folded and wound into drums for shipment without difficult as compared to rigid cables. Flexibility is thus a thing to consider especially during installation.

Extrusions
Triple extrusions form a clean electrode limiting unequal electrical stress. Thermosetting semi-conductor shields are extruded creating a high dielectric strength with a corresponding low dielectric loss. Shielding majorly helps in controlling the amount of stress acting on the cable hence improving the electrical conductivity of the cable.

Insulation
EPR insulation ensures that the safety of the user is not compromised since it is a semi-conducting compound, which do not allow the transfer of electric power thus preventing the user from unnecessary electrocution especially when handling the cable. Insulation of electrical cable is very important because not only does it protects the user but the cable as well. EPR offers an excellent heat, oil, moisture, corona, radiation and chemical resistance.

Jacketing
This is the outer coat that offers an additional protection to the cable against harsh environmental conditions. Anaconda Type MP-GC uniblend power cable is jacketed with a lead-cured Chlorinated Polyethylene (CPE) layer. It protects the cable against mechanical damages such as abrasions, tearing, punctures, oil and flame as well as corrosive chemicals and moisture. A cable with this kind of defensive attributes is the ideal cable for your wiring system as it will serve you for a much long time.

Applications
Anaconda Type MP-GC Mine Power cable is intended to serve in mining and bore-hole applications to drive heavy load machines with a power voltage rating not exceeding 15000V. It can be installed through direct burial, duct systems and aerial installations.

power conductors ampacity* 40°c
ambient temp
amercable and
tiger brand
part number
Action
size awg no. of wires
per conductor
2 3 164 16365.910200 Request a Quote
1 3 187 16365.910100 Request a Quote
1/0 3 215 16365.915100 Request a Quote
2/0 3 246 16365.915200 Request a Quote
3/0 3 283 16365.915300 Request a Quote
4/0 3 325 16354.396889 Request a Quote
250 3 359 16365.916000 Request a Quote
350 3 438 16362.279989 Request a Quote
500 3 536 16365.916500 Request a Quote