General Cable Anaconda® Brand Type G-CGC Power Round Portable w/Extensible Ground-Check EPR CPE 2000 Volts Three Conductor

General Cable Anaconda® Brand Type G-CGC Power Round Portable w/Extensible Ground-Check EPR CPE 2000 Volts Three Conductor

Product Details

Conductor: 1 AWG thru 500 kcmil coated annealed copper, bunched wires, rope-lay-stranded per ASTM B172 
Insulation: Ethylene Propylene Rubber (EPR) insulation colored (black, white and red) 

Ground-Check Conductor: 
• Coated copper specially stranded to provide extensibility without sustaining tensile load, thereby providing maximum resistance to flex fatigue 
• Insulated with high-strength polypropylene and placed in the center interstice 
Grounding Conductors: Three coated copper, rope-lay-stranded per ASTM B172 
Jacket: Reinforced, two-layer, extra-heavy-duty, leadcured Chlorinated Polyethylene (CPE) 
Jacket Marking: GENERAL CABLE® ANACONDA® BRAND (SIZE) 3/C TYPE G-CGC 2000 VOLTS P-7K-102-045 MSHA 
Options: 
• Colored jackets are available 
• Anamaxx® jacket 
Applications: 
• Designed for use as trailing cables on AC mining equipment: 
  - Where a ground-check conductor is required for fail-safe ground monitoring 
  - With wireless ground monitoring systems (The symmetrical grounding system does not produce induced voltages when operating in a balanced 3-phase system) 

Features: 
• Improved ground-check conductor has longer flex life and durability 
• Rope-lay-stranded conductors are extremely flexible and resistant to wire breakage 
• Symmetrical grounding system does not produce induced voltages when operating in a balanced 3-phase system 
• G-CGC can also be used as a Type G cable 
• Excellent heat, moisture, steam, oil, chemical and radiation resistance 
• Flexible for easy handling 
• Resists cutting, impact, abrasion, flame and sunlight 
• Excellent thermal stability and physical properties over a broad temperature range 
• Two-layer jacket is reinforced to provide maximum protection from mechanical damage— the cause of most portable cable failures 
Compliances: 
• ICEA S-75-381 Portable and Power Feeder Cables for use in mines and similar applications 
• Meets flame test requirements and is accepted for listing by MSHA 
• Approved by the Pennsylvania Department of Environmental Protection 

Packaging: Material cut to length and shipped on nonreturnable reels
cond. size
(awg/ kcmil)
no. of cond. ampacity general cable and
anaconda brand
part number
Action
1 3 161 13329.340100 Request a Quote
1/0 3 186 13329.345100 Request a Quote
2/0 3 215 13329.645200 Request a Quote
3/0 3 249 13329.645300 Request a Quote
4/0 3 287 13329.645400 Request a Quote
250 3 320 13329.646000 Request a Quote
350 3 394 13329.646200 Request a Quote
500 3 487 13329.646500 Request a Quote