Popular Products

  • HVTECK 3C 220 Mils TRXLPE Tape Shield PVC AIA PVC Power Shielded Armored 15kV CSA

    Select gauge from drop-down menu for prices:


    Free Shipping

    No End Date

    Click to View Shopping Cart

    Conductor: 2 AWG thru 750 kcmil bare copper compact Class B strand 

    Strand Shield: A thermoset semi-conducting strand shield is extruded over the conductor 

    Insulation: Tree-Retardant Cross-linked Polyethylene (TRXLPE) 

    Insulation Shield: 
    • This consists of a semi-conducting thermosetting layer, applied in a triple extrusion process, plus a helically applied gapped copper tape 
    • Color-coded: black, red or blue colored tape placed longitudinally under the copper tape shield 

    Ground (Bonding) Conductor: The conductor consists of one uninsulated stranded bare copper conductor 

    Inner Jacket: Lead-free, flame-retardant, moisture- and sunlight-resistant Polyvinyl Chloride (PVC), black 

    Armor: Aluminum Interlocked Armor (AIA) 

    Overall Jacket: Lead-free, ACID-FLAME-CHECK ✓✓® flameretardant, moisture- and sunlight-resistant Polyvinyl Chloride (PVC), red 

    Options: Galvanized Steel Interlocked Armor (GSIA) 

    Applications: 
    • For wiring in all hazardous locations when used with certified HL cable glands 
    • For exposed and concealed wiring in dry, damp or wet locations 
    • For use in ventilated, non-ventilated and laddertype cable trays in dry, damp or wet locations 
    • For direct earth burial (with protection as required by inspection authority) 

    Features: 
    • Rated at 90˚C wet or dry 
    • Excellent crush, oil and chemical resistance 
    • Provides long service life 
    • Cost-effective alternative to installations in conduit 
    • Meets cold bend and impact tests at -40˚C 

    Compliances: 
    Industry Compliances: 
    • CSA Standard C22.2 No. 131 and No. 174 
    • CSA Standard C68.10 

    Flame Test Compliances: 
    • CSA FT1 and FT4 
    • IEEE 383 (70,000 BTU/hr) 
    • UL 1581 (70,000 BTU/hr) 
    • IEEE 1202 (70,000 BTU/hr) CSA FT4 
    • ICEA T-30-520 (70,000 BTU/hr) 
    • ICEA T-29-520 (210,000 BTU/hr) 

    Other Compliances: 
    • Hazardous Location Rating: HL 
    • EPA 40 CFR, Part 261 for leachable lead content per TCLP method 
    • OSHA Acceptable 
    • RoHS Compliant 

    Packaging: 
    • For Canadian customers, lengths are provided on returnable wood or steel reels that require a deposit. Extra charges apply for lagging, pulling eyes, paralleling and plexing 
    • For U.S. customers, material cut to length and shipped on non-returnable wood reels, while lengths in excess of 10,000 lbs. are provided on returnable steel reels that require a deposit. Extra charges apply for cuts less than 1000 ft., lagging, pulling eyes, paralleling and plexing

    cond.
    size
    (awg/
    kcmil)
    no.of cond. ground wire size
    (awg)
    nominal diameter (over) copper weight net weightw/armor outdoor
    amp.**(40˚c
    ambient)
    general cable part
    number
    insulation
    (inches)
    insulation
    shield
    (inches)
    inner jacket
    (inches)
    armor (inches) cable
    (inches)
    lbs/1000 ft kg/km
    lbs/
    1000ft
    kg/km al steel al steel
    2
    3 6 0.76 0.83 2.02 2.31 2.43 793 1180 2665 3518 3966 5235 141 17496.230200*
    1
    3 6 0.79 0.86 2.10 2.37 2.49 964 1435 3089 3930
    4597 5850 161 17496.010100*
    1/0
    3 6 0.83 0.89 2.17 2.46 2.58 1175 1749 3300 4300 4900 6390 184 17451.316781*
    2/0
    3 6 0.86 0.93 2.26 2.55 2.67 1438 2140 3650 4690 5430 6980 212 17496.015200*
    3/0
    3 4 0.91 0.98 2.36 2.65 2.77 1821 2710 4140 5230 6160 7780 242 17496.025300*
    4/0
    3 4 0.96 1.03 2.47 2.76 2.88 2248 3345 4680 5810 6960 8650 278 17496.035400
    250
    3 4 1.02 1.08 2.59 2.88 3.00 2607 3880 5275 6440 7850 9580 306 17496.026000*
    350 3 3 1.12 1.20 2.90 3.19 3.33 3597 5353 6842 8170 10181 12160 373 17496.046200
    500 3 3 1.24
    1.32 3.16 3.45 3.59 5022 7474
    8513 10050 12668 14950 450 17496.056500
    750 3 2 1.42 1.51 3.57 3.85 4.00 7452 11090 11507 13160 17122 19580 545 17496.037000

    Quick Quote Form 

    * Indicates required field

    Receive A Response In 5 Minutes Or Less During Regular Business Hours