Popular Products

  • Type MC-HL XLPE 2000V Armored Power 3/C VFD UL Cable Tray Use Sunlight-Resistant Direct Burial UL Marine Shipboard Cable ABS CWCMC CCW

    Select gauge from drop-down menu for prices:


    Free Shipping

    No End Date

    Click to View Shopping Cart

    Conductor:
    • Bare annealed copper per ASTM B3 
    • 10 AWG and smaller are Class B compressed stranding per ASTM B
    • 8 AWG and larger are compact standing per ASTM B496

    Insulation:
    • Cross-linked Polyethylene (XLPE) insulation, 2000 V thicknesses per ICEA S-95-658 
    • Color-coded black with printed numbers per ICEA Method 4

    Grounding Conductors:
    • Class B stranded bare annealed copper per ASTM B3 and B8 
    • Three (3) split grounding wires per specification 9615 exceed the minimum required in NEC Table 250.122

    Cable Assembly: 
    • Insulated conductors and grounding wires are cabled together with nonhygroscopic fillers when required 
    • A binder tape is applied over the cabled core 

    CCW Armor: 
    • Impervious, continuously welded and corrugated aluminum alloy sheath per UL 1569 and UL 2225 
    • CCW armor conductivity meets the grounding requirements of NEC Article 250

    Jacket: 
    • Flame-retardant, moisture- and sunlight-resistant Polyvinyl Chloride (PVC) — Black 
    • Low temperature performance meets ASTM D746 brittleness temperature at or below -40°C

    Applications: 
    • Variable Frequency Drives: 3-conductor CCW armored cables with three (3) symmetrical grounding wires is the preferred wiring method for use with AC  motors controlled by pulse-width modulated Inverters in VFD applications 
    • CCW armored cables offer an economical, rugged and reliable alternative to labor-intensive cable in conduit wiring methods 
    • For use in Class I, II and III, Divisions 1 and 2; and Class I, Zones 1 and 2 hazardous locations per NEC Articles 501, 502 and 503 
    • For use as services, feeders and branch circuits for power, lighting, control, and signal circuits in accordance with NEC Articles 330 and 725 
    • Installed indoors or outdoors, wet or dry locations, directly buried, embedded in concrete, in a raceway, as aerial cable on a messenger, in cable trays, or as  exposed runs secured to supports in accordance with NEC Article 330 
    • Recognized for use on fixed or floating offshore petroleum facilities as recommended by the American Petroleum Institute

    Features: 
    • 90°C, 2000 V rated XLPE insulation with a dielectric constant less than 3.0 to withstand momentary voltage spikes common in certain VFD applications 
    • Three (3) oversized, symmetrical grounding wires recommended for use with pulse-width modulated AC drives 
    • CCW armor provides an impervious barrier to moisture, gas and liquids  
    • CCW armor provides EMI shielding performance 
    • Factory assembled and tested cable for use as an alternative to cable in conduit wiring systems 
    • Meets cold impact at -40°C 
    • 90°C continuous operating temperature, wet or dry 
    • 130°C emergency rating 
    • 250°C short circuit rating

    Specifications:
    Design Adherence:
     • ICEA S-95-658/WC70 Standard for Non-Shielded Power Cable, 2 kV or Less 
    • UL 44 Rubber Insulated Wires and Cables 
    • UL 1569 Metal Clad Cables 
    • UL 2225 Cables and Cable Fittings for Use in Hazardous Locations 
    • UL 1309 Marine Shipboard Cable

    Flame Tests: 
    • ICEA T-29-520 (210,000 BTU/hr) 
    • IEEE 383 (70,000 BTU/hr) 
    • CSA FT4 
    • IEEE 1202 (70,000 BTU/hr) 
    • UL 1581 (70,000 BTU/hr) 
    • IEC 332-3 Cat. A

    Compliances: 
    • UL Type MC-HL, SUN RES, CT USE, DIR BUR, -40°C, UL File # E90496 
    • UL Listed Marine Shipboard, UL File # E85994 
    • American Bureau of Shipping (ABS) Listed for CWCMC 
    • RoHS Compliant

    cond.
    size
    (awg/
    kcmil)
    no. of
    cond.
    insulation
    thickness
    bare
    ground
    (awg)
    nominal
    core o.d.
    nominal
    armor o.d.
    jacket
    thickness
    nominal
    overall o.d.
    approximate
    net weight
    90°c
    ampacity
    @ 30°c
    ambient¹
    General Cable
     Part Number

    mils mm inches mm inches mm mils mm inches mm lbs/
    1000 ft
    kg/
    1000 m
    14 (7/w)
    (2.08 mm²)
    3 60 1.52 3 x #18 0.44 11.1 0.62 15.2 50 1.27 0.73 17.9 267 397 15 9615.01403318
    12 (7/w)
    (3.31 mm²)
    3 60 1.52 3 x #16 0.47 11.9 0.66 16.2 50 1.27 0.77 18.9 324 482 20 9615.01203316
    10 (7/w)
    (5.26 mm²)
    3 60 1.52 3 x #14 0.53 13.3 0.73 17.8 50 1.27 0.84 20.5 400 595 30 9615.01003314
    8 (7/w)
    (8.36 mm²)
    3 70 1.78 3 x #14 0.65 16.5 0.86 21.1 50 1.27 0.97 23.8 524 780 55 9615.00803314
    6 (7/w)
    (13.3 mm²)
    3 70 1.78 3 x #12 0.71 18.0 0.96 23.4 50 1.27 1.07 26.1 697 1,037 75 9615.00603312
    4 (7/w)
    (21.2 mm²)
    3 70 1.78 3 x #12 0.81 20.6 1.09 26.6 50 1.27 1.23 30.1 1,000 1,488 95 9615.00403312
    2 (7/w)
    (33.6 mm²)
    3 70 1.78 3 x #10 0.94 23.9 1.25 30.6 50 1.27 1.36 33.3 1,285 1,912 130 9615.00203310
    1 (19/w)
    (42.4 mm²)
    3 90 2.29 3 x #10 1.13 28.7 1.48 36.1 50 1.27 1.59 38.8 1,595 2,374 150 9615.00103310
    1/0 (19/w)
    (53.5 mm²)
    3 90 2.29 3 x #10 1.21 30.6 1.55 38.0 60 1.52 1.68 41.2 1,930 2,872 170 9615.11003310
    2/0 (19/w)
    (67.4 mm²)
    3 90 2.29 3 x #6 1.30 32.9 1.68 41.0 60 1.52 1.81 44.2 2,507 3,731 195 9615.21003306
    4/0 (19/w)
    (107 mm²)
    3 90 2.29 3 x #4 1.53 38.7 1.91 46.7 60 1.52 2.04 49.9 3,590 5,342 260 9615.41003304
    250 (37/w)
    (127 mm²)
    3 105 2.67 3 x #4 1.71 43.4 2.12 51.8 60 1.52 2.25 55.1 4,150 6,176 290 9615.25003304
    350 (37/w)
    (177 mm²)
    3 105 2.67 3 x #2 1.93 48.9 2.41 58.9 75 1.91 2.57 62.8 5,214 7,759 350 9615.35003302
    500 (37/w)
    (253 mm²)
    3 105 2.67 3 x #1 2.20 55.8 2.68 65.5 75 1.91 2.84 69.5 6,977 10,382 430 9615.50003301

    Quick Quote Form 

    * Indicates required field

    Receive A Response In 5 Minutes Or Less During Regular Business Hours

    Captcha Image

    This product has no related products.