General Cable EmPowr® 115 Miles 5 kV 3/0 AWG Copper Wire PVC Jacket Link and Shielded Power Cable Al Conductor TRXLPE Insulation

General Cable EmPowr® 115 Miles 5 kV 3/0 AWG Copper Wire PVC Jacket Link and Shielded Power Cable Al Conductor TRXLPE Insulation

Select gauge from drop-down menu for prices:

General Cable EmPowr® 115 Miles 5 kV 3/0 AWG Copper Wire PVC Jacket Link and Shielded Power Cable Al Conductor TRXLPE Insulation
EmPowr 115 Miles 5 kV 3/0 AWG Copper Wire PVC Jacket Link and Shielded Power Cable Al Conductor TRXLPE Insulation

Complete Cable: Lead-free cross-linked semi-conducting conductor shield, insulation and semi-conducting insulation shield are extruded over a solid or stranded aluminum conductor and cured in a single operation. Uncoated copper wires (helically applied), separator tape and overlaying black PVC jacket are applied over the cable core. These products meet the latest requirements of ANSI/ICEA S-97-682 and AEIC CS8 as applicable for Tree-Retardant Cross-linked Polyethylene(TRXLPE) insulated shielded power cable.

Conductor: Solid or Class B compressed concentric lay stranded 1350 aluminum.

Conductor Shield: Extruded lead-free semi-conducting thermosetting polymeric stress control layer.

Insulation: Extruded unfilled lead-free Tree-Retardant Cross-linked Polyethylene (TRXLPE).

Insulation Shield: Extruded lead-free semi-conducting thermosetting layer, clean and free stripping from insulation.

Copper Wire Shield: Helically applied annealed solid bare copper wires with a lapped non-metallic tape serving as a binder/separator.

Jacket: Black, non-conducting, sunlight-resistant Polyvinyl Chloride (PVC).

Features and Benefits:
• Lead-free environmentally friendly cable
• Triple-extruded for clean interfaces
• Dry nitrogen cure for enhanced performance
• Class 10,000 environment utilized for cable core material handling
• Excellent moisture resistance
• High dielectric strength
• Low dielectric loss
• Excellent resistance to water treeing
• Clean-stripping insulation shield
• Sunlight-resistant

Temperature Rating:
• Normal - 90°C
• Emergency* - 130°C
• Short Circuit - 250°C

Applications: EmPowr® Link+ cables are intended for use in dry or wet locations for distribution of threephase medium-voltage power. These cables may be installed in ducts or direct buried.

Options:
• Copper conductors
• STRANDFILL® blocked conductor. Tested in accordance with ICEA T-31-610
• True Triple Extrusion
• UltraPowr® smoother and cleaner semi-conducting conductor shield
• Low-strip insulation shield
• 3 X 1/C triplex or parallel
• Type MV-90 UL 1072
• TRXLPE Class III insulation for 105°/140°C temperature rating
• Type MV-105 UL 1072
• UL Listed

technical specifications:
compressed conductor(al awg or kcmil) 3/0
compressed conductor(no.of wires) 19
copper neutral(no.of wires) 7
copper neutral(wire size awg)
22
diameter (1) inches (min. insulation ) 0.700
diameter (1) inches (max. insulation) 0.775
diameter (1) inches (pvc jacket) 1.001
nominal jacket thkn. inches (1) 0.080
approx. weight (1) lb/1000 ft(al cond.) 158
approx. weight (1) lb/1000 ft(cu wires) 15
approx. weight (1) lb/1000 ft(total)
454
ampacity (2)(direct buried) 280
ampacity (2)(in duct) 215

QUESTIONS & ANSWERS

Have a Question?

Be the first to ask a question about this.

Ask a Question