Prysmian Cable 500 MCM 3/C Copper Air Bag UL Type MV-105 25kV 133% Medium Voltage Commercial and Industrial Cable QPE570A

Prysmian Cable 500 MCM 3/C Copper Air Bag UL Type MV-105 25kV 133% Medium Voltage Commercial and Industrial Cable QPE570A

Select gauge from drop-down menu for prices:

Prysmian Cable 500 MCM 3/C Copper Air Bag UL Type MV-105 25kV 133% Medium Voltage Commercial and Industrial Cable QPE570A

Product Details

Three conductor cable with stranded copper conductors, extruded insulation system consisting of a thermosetting semiconducting conductor shield, high dielectric strength EPROTENAX™ EPR insulation, thermosetting semiconducting insulation shield, helically applied bare copper tape shield, cabled with fillers and grounding conductors, overall binder tape, Air Bag™ foamed polymeric layer for superior mechanical protection and overall sun resistant PVC jacket. Suitable for Class I Division 2 locations. 

Conductor: Class B Compact concentric strand aluminum alloy 1350 or soft drawn annealed copper per ASTM. 

Conductor Shield: Extruded thermosetting semiconducting shield which is free stripping from the conductor and bonded to the insulation. 

Insulation: Natural high dielectric strength EPROTENAX™ EPRbased insulation, combined with other materials and agents that enhance the electrical and mechanical characteristics assuring extended cable life. 

Insulation shield: Extruded thermosetting semiconducting shield with controlled adhesion to the insulation providing the required balance between electrical integrity and ease of stripping. 

Metallic Shield: Helically applied non-magnetic copper tape(s) over the insulation shield with a minimum overlap of 25%. A Mylar ribbon is longitudinally applied under the copper tape shield for phase identification - 1C w/ Red, 1C w/ Blue, and 1C w/ Black. 

Grounding Conductors: Bare stranded copper conductor per UL, ICEA, and ASTM. ASSEMBLY: Phase identified conductors cabled with fillers and a grounding conductor, forming a firm and cylindrical cable core. A binder tape is applied to maintain core symmetry & mechanical stability. 

Mechanical Protection: High strength and high crush resistant Air Bag™ layer extruded over the core assembly. JACKET: Sunlight and moisture resistant polyvinyl chloride (PVC) jacket. 

Specifications and Ratings: 
• ICEA S-93-639/NEMA WC74 Type MV-105 
• UL 1072 For CT USE 
• Direct Buried 
• Sunlight Resistant 
• IEEE 383 Flame Test 
• IEEE 1202 Flame Test 
• CSA Cold Impact/Bend Test (-40C) 
• MSHA CSA FT4 Flame Test 
• ICEA T-29-520 at 210,000 BTU/hr 
• Type MP

technical specification:
conductor 500 MCM CU
insulation thickness (mils) 320
ground wires no. 3
ground wires size 5 AWG
conductor diameter (in) (a) 0.742
insulation diameter (in) (b) 1.43
insulation shield diameter (in) (c) 1.49
overall jacket diameter (in) (d) 3.76
cable weight (lbs/kft) 11748
minimum bending radius (in) 27
ampacity (amps) ‡105°c in duct 485
ampacity (amps) ‡105°c in air/tray 600
impedance (micro-ohms/foot) pos/neg seq 29 + j38
impedance (micro-ohms/foot) zero seq. 400 + j22
prysmian cable part number QPE570A