General Cable EmPowr® 35 kV 345Mils 350kcmil Longitudinally Applied Corrugated Tape 1.787 LLDPE Jacket Fill Shielded Power Cable Al Cond. EPR Insulation

General Cable EmPowr® 35 kV 345Mils 350kcmil Longitudinally Applied Corrugated Tape 1.787 LLDPE Jacket Fill Shielded Power Cable Al Cond. EPR Insulation

Select gauge from drop-down menu for prices:

General Cable EmPowr® 35 kV 345Mils 350kcmil Longitudinally Applied Corrugated Tape 1.787 LLDPE Jacket Fill Shielded Power Cable Al Cond. EPR Insulation

Product Details

Complete Cable: Cross-linked semi-conducting conductor shield, insulation and semi-conducting insulation shield are extruded over a solid or stranded aluminum conductor and cured in a single operation. Corrugated copper tape and an extruded black jacket are applied over the cable core. These products meet the latest requirements of ANSI/ICEA S-97-682 and AEIC CS8 as applicable for Ethylene Propylene Rubber (EPR) insulated shielded power cable.

Conductor: Solid or Class B compressed concentric lay stranded 1350 aluminum.

Conductor Shield: Extruded semi-conducting thermosetting polymeric stress control layer.

Insulation: Extruded Ethylene Propylene Rubber (EPR) Class II and III.

Insulation Shield: Extruded semi-conducting thermosetting layer, clean and free stripping from insulation.

Longitudinally Applied Corrugated Tape: Copper, 8 or 10 mil thick Longitudinally Applied Corrugated Tape (LACT) with a minimum 375 mil overlap.

Jacket: Black, non-conducting, sunlight-resistant, Linear Low-Density Polyethylene (LLDPE).

Features and Benefits:
• Even distribution of fault current and better heat dissipation
• Allows expansion/contraction of cable core
• Improved bending characteristics versus helical copper tape shield
• Triple-extruded for clean interfaces
• Class 10,000 environment utilized for cable core material handling
• Flexibility for easy handling
• Excellent moisture resistance
• Deformation-resistant
• High dielectric strength
• Low dielectric loss
• Excellent resistance to water treeing
• Clean-stripping insulation shield without the use of a release agent
• Sunlight-resistant

Temperature Rating:
• Normal - 105°C
• Emergency* - 140°C
• Short Circuit - 250°C

Applications: EmPowr® Fill cables are intended for use in dry or wet locations for distribution of three-phase medium-voltage power. These cables may be installed in ducts or direct buried.

Options:
• Copper conductors
• EmPowr® Fill LF Lead-Free EAM
• STRANDFILL® blocked conductor. Tested in accordance with ICEA T-31-610
• BIFILL® tested to ICEA T-34-664 1. blocked conductor 2. blocked cable core/LACT
• TRIFILL® tested to ICEA T-34-664 1. blocked conductor 2. blocked cable core/LACT 3. sealed overlap and blocked LACT/jacket
• Sealed LACT overlap
• Dry nitrogen cure
• True Triple Extrusion
• Red stripes on jacket
• Semi-conducting thermoplastic jacket
• 3 X 1/C triplex or parallel
• Type MV-90 UL 1072
• UL Listed

technical specifications:
compressed conductor(al awg or kcmil) 350
compressed conductor(no. of wires) 37
diameter (1) inches(insulation in min.) 1.355
diameter (1) inches(insulation in max.) 1.455
diameter (1) inches(lact shield - thkn.) 0.010
diameter (1) inches(lact shield - o.d.) 1.567
diameter (1) inches(lldpe jacket) 1.787
nominal jacket thkn. inches(1) 0.110
approx. weight (1) lb/1000 ft(al cond) 329
pprox. weight (1) lb/1000 ft(cu shield)
243
approx. weight (1) lb/1000 ft(total) 1640
ampacity (2)(direct buried) 430
ampacity (2)(in duct) 355

QUESTIONS & ANSWERS

Have a Question?

Be the first to ask a question about this.

Ask a Question