  • VNTC Nylon PVC Type TC-ER1 (14 AWG-10 AWG) E-2 Color Code Control Unshielded 600V UL

    Select gauge from drop-down menu for prices:


    Free Shipping

    No End Date

    Click to View Shopping Cart

    Conductor:
    • 14 AWG thru 10 AWG fully annealed stranded bare copper per ASTM B3
    • Class B stranding per ASTM B8

    Insulation:
    • Flame-retardant Polyvinyl Chloride (PVC) with Polyamide (nylon)
    • Color-coded per ICEA Method 1, Table E-2 plus alpha-numeric printed numbers (does not include white or green)

    Jacket: Lead-free, flame-retardant, sunlight-resistant Polyvinyl Chloride (PVC)

    Applications:
    • In free air, raceways and direct burial
    • In wet or dry locations
    • Approved for direct burial
    • Class I, Division 2 industrial hazardous locations per NEC
    • Permitted for Exposed Run (ER) use in accordance with NEC for 3 or more conductors

    Features:
    • Rated at 90˚C dry, 75˚C wet
    • Ripcord applied to all cables with jacket thickness of 60 mils or less
    • Provides outstanding sunlight, cold bend and cold impact resistance
    • Offers the smallest cable O.D. available for suitable applications
    • Provides long service life
    • Provides good oil and chemical resistance
    • Meets cold bend test at -25˚C
    • Meets the crush and impact requirements of Type MC cable

    Compliances:
    Industry Compliances:
    • UL 83 NEC Type THHN/THWN conductors
    • UL 1277 Type TC-ER for 3 or more conductors, UL File # E57179
    • UL 1581
    • ICEA S-73-532/NEMA WC57

    Flame Test Compliances:
    • UL 1685 Vertical Flame Test
    • IEEE 383
    • IEEE 1202
    • CSA FT4

    Other Compliances:
    • EPA 40 CFR, Part 261 for leachable lead content per TCLP
    • OSHA Acceptable
    • RoHS Compliant

    Packaging: Material cut to length and shipped on non-returnable wood reels

    cond.
    size
    (AWG)
    no.
    of
    cond.
    cond.
    strand
    minimum avg.
    insulation
    thickness
    minimum avg.
    jacket
    thickness
    nominal
    cable o.d.
    copper
    weight
    net
    weight
    general
    cable
    part
    number
    inches mm inches mm inches mm lbs/
    1000ft
    kg/
    km
    lbs/
    1000ft
    kg/
    km
    14 AWG conductors
    14 2 Flat 7W 0.020 0.51 0.045 1.14 0.210 x 0.320 5.33 x 8.13 25 37 54 80 235040
    14 2 7W 0.020 0.51 0.045 1.14 0.320 8.13 26 39 64 95 245590*
    14 3 7W 0.020 0.51 0.045 1.14 0.345 8.76 39 58 80 119 235050
    14 4 7W 0.020 0.51 0.045 1.14 0.365 9.27 52 77 100 149 235060
    14 5 7W 0.020 0.51 0.045 1.14 0.410 10.41 65 97 118 176 235070
    14 7 7W 0.020 0.51 0.045 1.14 0.445 11.30 90 134 153 228 235080
    14 9 7W 0.020 0.51 0.060 1.52 0.505 12.83 116 173 213 317 235090
    14 12 7W 0.020 0.51 0.060 1.52 0.595 15.11 155 231 267 397 235110
    14 19 7W 0.020 0.51 0.060 1.52 0.695 17.65 245 365 396 589 235130
    14 25 7W 0.020 0.51 0.060 1.52 0.785 19.94 323 481 507 755 235150
    14 30 7W 0.020 0.51 0.080 2.03 0.895 22.73 387 576 637 948 235160*
    14 37 7W 0.020 0.51 0.080 2.03 0.970 24.64 478 711 766 1140 235170
    12 AWG conductors
    12 2 Flat 7W 0.020 0.51 0.045 1.14 0.225 x 0.360 5.72 x 9.14 40 60 74 110 234580
    12 2 7W 0.020 0.51 0.045 1.14 0.355 9.02 41 61 85 127 260150*
    12 3 7W 0.020 0.51 0.045 1.14 0.385 9.78 62 92 131 195 234590
    12 3+Grnd 7W 0.020 0.51 0.045 1.14 0.385 9.78 83 124 131 195 255090
    12 3 7W 0.020 0.51 0.045 1.14 0.385 9.78 62 92 131 195 277460²
    12 4 7W 0.020 0.51 0.045 1.14 0.420 10.67 83 124 138 205 234600
    12 5 7W 0.020 0.51 0.045 1.14 0.445 11.30 108 160 165 246 226420
    12 7 7W 0.020 0.51 0.045 1.14 0.490 12.45 144 214 217 323 234620
    12 9 7W 0.020 0.51 0.060 1.52 0.605 15.37 185 275 297 442 226500
    12 12 7W 0.020 0.51 0.060 1.52 0.675 17.15 247 368 377 561 234640
    12 19 7W 0.020 0.51 0.060 1.52 0.785 19.94 391 582 568 845 243600
    12 25 7W 0.020 0.51 0.080 2.03 0.940 23.88 515 767 775 1153 243610*
    12 30 7W 0.020 0.51 0.080 2.03 1.030 26.16 618 920 919 1368 321720*
    12 37 7W 0.020 0.51 0.080 2.03 1.105 28.07 762 1134 1100 1637 234680*
    10 AWG conductors
    10 2 Flat 7W 0.026 0.66 0.045 1.14 0.260 x 0.425 6.60 x 10.80 64 95 108 161 236300
    10 2 7W 0.026 0.66 0.045 1.14 0.420 10.67 65 97 115 171 243630*
    10 3 7W 0.026 0.66 0.045 1.14 0.450 11.43 131 195 191 284 236310
    10 3+Grnd 7W 0.026 0.66 0.045 1.14 0.450 11.43 131 195 191 284 255080
    10 4 7W 0.026 0.66 0.045 1.14 0.505 12.83 135 200 209 311 236320
    10 5 7W 0.026 0.66 0.060 1.52 0.570 14.48 169 252 268 399 236330
    10 7 7W 0.026 0.66 0.060 1.52 0.620 15.75 236 351 350 521 236340
    10 9 7W 0.026 0.66 0.060 1.52 0.725 18.42 295 440 440 655 243620*
    10 12 7W 0.026 0.66 0.060 1.52 0.815 20.70 404 602 584 869 236350