Conductor:
• 14 AWG thru 10 AWG fully annealed stranded bare copper per ASTM B3
• Class B stranding per ASTM B8

Insulation:
• Flame-retardant Cross-linked Polyethylene (XLPE)
• Color-coded per ICEA Method 1, Table E-2 (does not include white or green)

Jacket: Lead-free, flame-retardant, sunlight-resistant Polyvinyl Chloride (PVC)

Applications:
• In free air, raceways and direct burial
• In wet or dry locations
• Approved for direct burial
• Class I, Division 2 industrial hazardous locations per NEC
• Permitted for Exposed Run (ER) use in accordance with NEC for 3 or more conductors

Features:
• Rated at 90?C wet or dry
• Ripcord applied to all cables with jacket thickness of 60 mils or less
• Excellent electrical properties
• Abrasion- and chemical-resistant
• Sunlight- and weather-resistant
• Meets cold bend test at -25?C
• Meets the crush and impact requirements of Type MC cable

Compliances:
Industry Compliances:
• UL 44 Type XHHW-2
• UL 1277 Type TC-ER for 3 or more conductors, UL File # E57179
• UL 1581
• ICEA S-73-532/NEMA WC57

Flame Test Compliances:
• UL 1581/UL 2556 VW-1
• UL 1685 Vertical Flame Test
• IEEE 383
• IEEE 1202
• ICEA T-29-520
• CSA FT4

Other Compliances:
• EPA 40 CFR, Part 261 for leachable lead content per TCLP
• OSHA Acceptable
• RoHS Compliant

Packaging: Material cut to length and shipped on non-returnable wood reels

technical specification:
cond. size (awg) 12
no. of cond. 2 Flat
cond. strand 7W
minimum avg. insulation thickness(inches) 0.030
minimum avg. insulation thickness(mm) 0.76
minimum avg. jacket thickness(inches) 0.045
minimum avg. jacket thickness(mm) 1.14
nominal cable o.d.(inches) 0.245 x 0.400
nominal cable o.d.(mm) 6.22 x 10.16
copper weight(lbs/1000 ft) 40
copper weight(kg/km) 60
net weight(lbs/1000 ft) 86
net weight(kg/km) 128