General Cable XHHW-2 CT® 4/0 Gauge XLPE Low-Voltage Power 600 V UL Type XHHW-2 CT Rated Single Conductor Copper
Select gauge from drop-down menu for prices:
- General Cable XHHW-2 CT® XLPE Low-Voltage Power 600 V UL Type XHHW-2 CT Rated Single Conductor Copper
- General Cable XHHW-2 CT® 14 Gauge XLPE Low-Voltage Power 600 V UL Type XHHW-2 CT Rated Single Conductor Copper
- General Cable XHHW-2 CT® 12 Gauge XLPE Low-Voltage Power 600 V UL Type XHHW-2 CT Rated Single Conductor Copper
- General Cable XHHW-2 CT® 10 Gauge XLPE Low-Voltage Power 600 V UL Type XHHW-2 CT Rated Single Conductor Copper
- General Cable XHHW-2 CT® 8 Gauge XLPE Low-Voltage Power 600 V UL Type XHHW-2 CT Rated Single Conductor Copper
- General Cable XHHW-2 CT® 6 Gauge XLPE Low-Voltage Power 600 V UL Type XHHW-2 CT Rated Single Conductor Copper
- General Cable XHHW-2 CT® 4 Gauge XLPE Low-Voltage Power 600 V UL Type XHHW-2 CT Rated Single Conductor Copper
- General Cable XHHW-2 CT® 2 Gauge XLPE Low-Voltage Power 600 V UL Type XHHW-2 CT Rated Single Conductor Copper
- General Cable XHHW-2 CT® 1 Gauge XLPE Low-Voltage Power 600 V UL Type XHHW-2 CT Rated Single Conductor Copper
- General Cable XHHW-2 CT® 1/0 Gauge XLPE Low-Voltage Power 600 V UL Type XHHW-2 CT Rated Single Conductor Copper
- General Cable XHHW-2 CT® 2/0 Gauge XLPE Low-Voltage Power 600 V UL Type XHHW-2 CT Rated Single Conductor Copper
- General Cable XHHW-2 CT® 3/0 Gauge XLPE Low-Voltage Power 600 V UL Type XHHW-2 CT Rated Single Conductor Copper
- General Cable XHHW-2 CT® 250MCM XLPE Low-Voltage Power 600 V UL Type XHHW-2 CT Rated Single Conductor Copper
- General Cable XHHW-2 CT® 350MCM XLPE Low-Voltage Power 600 V UL Type XHHW-2 CT Rated Single Conductor Copper
- General Cable XHHW-2 CT® 500MCM XLPE Low-Voltage Power 600 V UL Type XHHW-2 CT Rated Single Conductor Copper
- General Cable XHHW-2 CT® 600MCM XLPE Low-Voltage Power 600 V UL Type XHHW-2 CT Rated Single Conductor Copper
- General Cable XHHW-2 CT® 750MCM XLPE Low-Voltage Power 600 V UL Type XHHW-2 CT Rated Single Conductor Copper
Conductor:
• 14 AWG thru 750 kcmil annealed bare copper per ASTM B3
• Class B stranding per ASTM B8
Insulation: Flame-retardant Cross-linked Polyethylene (XLPE)
Options:
• Tinned copper conductor
• Full colored insulation
Applications:
• General purpose building wire for use primarily in conduit or other recognized raceways as specified in the National Electrical Code
• Industrial environments where superior insulation toughness and chemical resistance are required
• Maximum operating temperature not to exceed 90?C in dry or wet locations
• In free air, raceways or cable trays in accordance with NEC
Features:
• Low Friction for easy pulling on 8 AWG and larger
• “FOR CT USE” on 1/0 AWG and larger
• Sunlight-resistant for 1/0 AWG and larger, all colors
• Rated at 90?C wet or dry
• Smaller cable O.D.
• Excellent electrical, thermal and physical properties
• Excellent resistance to moisture
• Excellent resistance to crush, compression cuts and heat deformation
Compliances:
Industry Compliances:
• National Electric Code (NEC)
• UL 44 Standard for Rubber Insulated Wire and Cable
• ICEA S-95-658/NEMA WC70
• UL Listed as Type XHHW-2, UL File # E90494
• OSHA Acceptable
Flame Test Compliances: UL 1685, 1/0 AWG and larger
Packaging: Material cut to length and shipped on non-returnable wood reels
technical specification: | |
cond.size(awg/kcmil) | 4/0 |
cond.strand
|
19/.1055 |
nominal cond.diameter(inches) | 0.51 |
nominal cond.diameter(mm) | 12.95 |
minimum avg.insulation thickness(inches) | 0.055 |
minimum avg.insulation thickness(mm) | 1.40 |
nominal cableo.d.(inches) | 0.63 |
nominal cable o.d.(mm) | 16.00 |
copper weight(lbs/1000 ft) | 653 |
copper weight(kg/km) | 972 |
net weight(lbs/1000 ft) | 706 |
net weight(kg/km) | 1051 |
ampacity (1)(60°c) | 195 |
ampacity (1)(75°c) | 230 |
ampacity (1)(90°c) | 260 |
catalog number | 5175.410 |