5KV UL Type MV-105, MC-HL, Shielded, EPR - HW310 00203

5KV UL Type MV-105, MC-HL, Shielded, EPR - HW310 00203

5KV UL Type MV-105, MC-HL, Shielded, EPR - HW310 00203
Technical Specifications:
Catalog Number HW310 00203
Size AWG/kcmil 2
No. of Conductors 3
No. of Strands 7
Insulation Thickness Mils 115
Jacket Thickness Mils 60
Ground Wire Size AWG 6
Class 1 Div. 1 Connector No. 424MA07
Rain Tight Connector No. 416MC08
Armor Diameter Inch 1.80
Overall Diameter Inch 1.92
Net Weight Lbs/Mft 1880

Specifications:

  • Impervious Continuously Welded Armor - Power Cable
  • 5KV UL Type MV-105, MC-HL, CT Use, 105°C
  • Shielded, EPR Insulation
  • 100% and 133% Insulation Level
  • Aluminum Armor
  • Copper Conductors

Application:
For use in harsh environments where maximum conductor protection is required. Used for primary power and feeder circuits in a broad range of commercial and industrial power distribution systems. Approved for use in wet or dry locations at 105°C, for installation indoors or outdoors, aerially, in conduits, ducts, cable trays or direct burial in circuits not exceeding 5000 volts. UL listed, Type MC-HL per UL Standard 2225 for use in Class I, Division I hazardous locations. UL approved for use at 105°C for continuous operation, 140°C for emergency overload conditions, and 250°C for short circuit conditions. Impervious continuously welded and corrugated aluminum armor cable is recommended as an economical alternative to wire in conduit systems.

Conductors:
Soft bare annealed copper per ASTM B-3, Class B stranding per ASTM B-8 (compressed) or ASTM B-496 (compact), with a semi-conducting conductor shield.

Insulation:
Ethylene propylene rubber (EPR) per ICEA S-97-682/S-93-639 with a semi-conducting insulation shield.

Shield:
Uncoated 5 mil copper tape with a minimum of 12.5% overlap.

Grounding Conductor:
Soft bare annealed copper per ASTM B-3, Class B stranding per ASTM B-8 sized in accordance with UL Standard 1072.

Armor:
Impervious continuously welded and corrugated aluminum.

Jacket:
Yellow flame-retardant and sunlight-resistant PVC.

Flame Tests:

ICEA 70,000 BTU/hr and 210,000 BTU/hr flame test

Color Code:

ICEA Method 4

Additional Standards:

  • UL listed, NEC Type MV-105 and Type MC, UL Standard 1072.
  • Single conductors are qualified per AEIC CS8.
  • UL listed Type CWCMC to IEEE 45/IEEE 1580 (46 CFR Part 111.60-23) Marine Shipboard Cable.
  • Meets requirements of CSA-C22.2 No. 0.3, -40°C cold impact test.

Connectors:

  • Explosion Proof, Class I Division 1: 424MA series - all nickel-plated aluminum
  • Rain Tight: 416MC series - all nickel-plated brass

QUESTIONS & ANSWERS

Have a Question?

Be the first to ask a question about this.

Ask a Question