  • PowrNet Underground Network Cable 600V Single Copper Conductor EAM Insulation LSZH Jacket

    Select gauge from drop-down menu for prices:


    Free Shipping

    No End Date

    Click to View Shopping Cart

    Complete Cable: General Cable’s PowerNet® 600 V network cables consist of a Class B compressed copper conductor, covered with EAM insulation and a black Low-Smoke, Zero-Halogen (LSZH), flameretardant, lead-free thermoset jacket. All cables are manufactured and tested in accordance with ANSI/NEMA WC70/ICEA S-95-658.

    Conductors: Class B compressed copper meeting the requirements of ASTM B8.

    Insulation/Jacket: The extruded thermoset, flame-retardant EAM insulation meets the requirements of an EPR Type II (Class E-2) insulation of ANSI/NEMA WC70/ICEA S-95-658. The extruded thermoset black jacket is a Type II Low-Smoke, Zero-Halogen (LSZH), flameretardant, lead-free thermoset polyolefin and meets the requirements of ANSI/NEMA WC70/ ICEA S-95-658.

    Features and Benefits: General Cable’s PowrNet 600 V network cable was developed for use in congested urban networks (particularly in duct systems) where high-reliability, easy-to-install low-smoke and -fume cables are needed. This unique cable design provides advantages of a track-resistant, low-smoke and reduced-gas evolution in the event of a fire. These installed performance features are complemented by excellent abrasion and tear resistance properties coupled with a low coefficient of friction which allows easy pulling into existing duct systems. PowrNet is rated 600 V and has a wet and dry conductor operating temperature rating of 90°C.

    Applications: General Cable’s PowerNet cable was engineered for use in congested urban secondary network duct and buried systems in wet or dry locations where maximum reliability, ease of installation, and low-smoke cables are required.

    Options:
    • Multiplexed constructions of 2 to 6 conductors
    • Multiplexed with bare ground conductors
    • Compact copper conductors
    • Tinned copper conductors
    • Type RHH/RHW-2 per UL 44
    • Type USE-2 per UL 854
    • UL OIL RES I (PR 1)
    • UL ST-1 limited smoke designation (sizes 1/0 AWG and larger)
    • UL “For CT Use” (sizes 1/0 AWG and larger)
    • EPR insulation
    • 2000 V rating

    size
    awg/
    kcmil
    no.
    of
    wires
    nom.
    cond.
    o.d.
    ins./jacket
    nom. thkn.
    inches
    nom.
    o.d.
    inches
    approx. weight
    lb/1000 ft
    ampacity (1)
    copper total direct
    buried
    in duct
    (2)
    6 7 0.178 0.045 / 0.030 0.34 81 120 120 80
    4 7 0.225 0.045 / 0.030 0.39 129 176 155 105
    2 7 0.283 0.045 / 0.030 0.44 205 262 200 140
    1 19 0.313 0.055 / 0.045 0.52 258 341 225 165
    1/0 19 0.352 0.055 / 0.045 0.56 326 416 255 190
    2/0 19 0.395 0.055 / 0.045 0.61 411 510 290 215
    3/0 19 0.443 0.055 / 0.045 0.65 518 627 330 250
    4/0 19 0.498 0.055 / 0.045 0.71 653 774 375 280
    250 37 0.558 0.065 / 0.065 0.83 772 949 410 315
    350 37 0.641 0.065 / 0.065 0.91 1081 1280 490 390
    500 37 0.789 0.065 / 0.065 1.06 1544 1783 590 475
    750 61 0.968 0.065 / 0.065 1.27 2316 2632 720 585
    1000 61 1.117 0.065 / 0.065 1.42 3088 3448 820 670