Power Cable 5KV/8KV UL Type MV-105-LS, 105°C Single Conductor, Shielded EPR Insulation Low Smoke Zero Halogen Jacket 5KV 133%, 8KV 100% Insulation Level Copper Conductor

Power Cable 5KV/8KV UL Type MV-105-LS, 105°C Single Conductor, Shielded EPR Insulation Low Smoke Zero Halogen Jacket 5KV 133%, 8KV 100% Insulation Level Copper Conductor

Select gauge from drop-down menu for prices:

Power Cable 5KV/8KV UL Type MV-105-LS, 105°C Single Conductor, Shielded EPR Insulation Low Smoke Zero Halogen Jacket 5KV 133%, 8KV 100% Insulation Level Copper Conductor

Product Details

Specifications:

  • HW 220 Power Cable
  • 5KV/8KV UL Type MV-105-LS, 105°C
  • Single Conductor, Shielded
  • EPR Insulation
  • Low Smoke Zero Halogen Jacket
  • 5KV 133%, 8KV 100% Insulation Level
  • Copper Conductor

Application:
LifeGuard™ Low Smoke Zero Halogen cable is for use in power circuits in chemical plants, refineries, steel mills, industrial plants, commercial buildings, utility substations and generating stations. It may be installed in open air, conduit, duct, cable tray when CT rated, or direct buried in earth, in wet and dry locations. It is highly flame retardant, produces very small amounts of smoke when burned and contains no halogens. LifeGuard™ cable is ideal for applications where a high degree of safety and equipment protection is required.
It is National Electric Code approved for use at 105°C for continuous operation, 140°C for emergency overload conditions, and 250°C for short circuit conditions.

Conductors:

  • Product Features:
  • Cable tray rated on sizes 1/0 AWG and larger
  • Sunlight-resistant
  • Approved for direct burial
  • Very low smoke production when burned
  • Highly chemical resistant
  • Very flame retardant
  • Burns to an ash - does not exhibit thermoplastic drip
  • Excellent compression and impact resistance
  • Superior tensile strength and abrasion resistance
  • Flexible jacket with low coefficient of friction

Conductors:
Compressed soft annealed copper per ASTM B-3, Class B stranding per ASTM B-8, with a semi-conducting conductor shield

Insulation:
Ethylene propylene rubber (EPR) per ICEA S-97-682 Type III with a semi-conducting insulation shield

Shield:
Uncoated copper tape with a 25% overlap per ICEA S-97-682

Jacket:
Sunlight-resistant and flame-retardant, Low Smoke Zero Halogen polyolefin per UL Standard 1072 and ICEA T-33-655-1994 Section 5-4

Flame Tests:

  • IEEE 383 70,000 BTU/hr flame test
  • IEEE 1202 70,000 BTU/hr flame test
  • UL Standard 1685 70,000 BTU/hr Flame Propagation and Smoke Release Test

Additional Standards:
AEIC C5-8

Size (AWG
or kcmil)
No. of
Strands
Net Weight Overall Diameter
(Inches)
Insulation
Thickness (Mils)
Jacket
Thickness
 (Mils)
Insulation
Diameter (Inch)
Product
Code
6 Gauge 7 286 0.63 115 60 0.43 HW220 00601 /
HW22000601
4 Gauge 7 350 0.71 115 60 0.50 HW220 00401 /
HW22000401
2 Gauge 7 460 0.77 115 60 0.56 HW220 00201 /
HW22000201
1 Gauge 19 565 0.81 115 60 0.60 HW220 00101 /
HW22000101
1/0 19 620 0.84 115 60 0.64 HW220 10101 /
HW22010101
2/0 19 755 0.93 115 80 0.68 HW220 20101 /
HW22020101
3/0 19 890 0.99 115 60 0.73 HW220 30101 /
HW22030101
4/0 19 1055 1.04 115 80 0.79 HW220 40101 /
HW22040101
250 MCM 37 1205 1.09 115 80 0.85 HW220 25001 /
HW22025001
350 MCM 37 1570 1.20 115 80 0.95 HW220 35001 /
HW22035001
500 MCM 37 2115 1.34 115 80 1.08 HW220 50001 /
HW22050001
750 MCM 61 2995 1.53 115 80 1.27 HW220 75001 /
HW22075001
1000 MCM 61 3870 1.68 115 80  1.42 HW220 10001 /
HW22010001

QUESTIONS & ANSWERS

Have a Question?

Be the first to ask a question about this.

Ask a Question