Power Cable 25KV/35KV UL - 350 MCM

Power Cable 25KV/35KV UL - 350 MCM

Power Cable 25KV/35KV UL - 350 MCM
Technical Specifications:
Size (AWG or kcmil): 350 MCM
No. of Strands 37
Insulation Thickness (Mils): 345
Jacket Thickness (Mils): 80
Insulation Diameter (Inch): 1.43
Overall Diameter (Inch): 1.69
Net Weight (Lbs.): 2205

Specifications:

  • HW 211
  • Power Cable - Unishield
  • 25KV/35KV UL Type MV-105, 105°C
  • Single Conductor, Shielded
  • EPR Insulation, PVC Jacket
  • 25KV 133%, 35KV 100% Insulation Level
  • Copper Conductor

Application:
For use in power circuits up to 35KV when installed in open air, conduit, duct, cable tray when CT rated, or direct buried in earth, in wet and dry locations. Used for applications in chemical plants, refineries, steel mills, industrial plants, commercial buildings, utility substations and generating stations. UL approved for use at 105°C for continuous operation, 140°C for emergency overload conditions, and 250°C for short circuit conditions.

Conductors:
Soft bare annealed copper per ASTM B-3, Class B stranding per ASTM B-8 (compressed) or ASTM B-496 (compact), with a semi-conducting conductor shield.

Insulation:
Ethylene propylene rubber (EPR) per ICEA S-97-682.

Shield:
Uncoated copper tape with a minimum 12.5% overlap per ICEA S-97-682.

Jacket:
Sunlight-resistant PVC per ICEA S-97-682 and UL Standard 1072.

Flame Tests:
IEEE 383 70,000 BTU/hr flame test – CT-rated material.

Additional Standards:

  • ICEA S-93-639
  • NEMA WC74
  • AEIC CS8
  • Federal Specification J-C-30B

Note:
CT ratings are available on sizes 1/0AWG and larger.

QUESTIONS & ANSWERS

Have a Question?

Be the first to ask a question about this.

Ask a Question