    Conductor: 
    • Bare annealed copper per ASTM B3 
    • Compact stranding per ASTM B496 

    Extruded Strand Shield (ESS): Extruded thermoset semi-conductor stress control layer over the conductor per ICEA S-93-639 and UL 1072 

    Insulation: 345 mils Ethylene Propylene Rubber (EPR) insulation per ICEA S-93-639 and UL 1072 

    Extruded Insulation Shield (EIS): Thermoset semi-conducting polymeric layer, free stripping from the insulation per ICEA S-93-639 and UL 1072 

    Shield:  5 mil annealed bare copper tape with 25% overlap 

    Phase Identification: Color-coded polymeric identification tape laid under the shield – black, red and blue 

    Grounding Conductors: 
    • Class B stranded bare annealed copper grounding conductor 
    • Sized in accordance with UL 1072 and NEC Article 250 

    Cable Assembly: 
    • Insulated and grounding conductors are cabled together with non-hydroscopic fillers when required 
    • Binder tape is applied over the cabled core 

    CCW Armor: 
    • Impervious, continuously welded and corrugated aluminum alloy sheath per UL Standards 1569 and 2225 
    • CCW armor conductivity meets the grounding requirements of NEC Article 250 

    Jacket: 
    • Flame-retardant, moisture- and sunlight-resistant Polyvinyl Chloride (PVC), black 
    • Low temperature performance meets ASTM D746 brittleness temperature at or below -60°C 

    Applications: 
    • CCW armored medium-voltage power cables offer an economical, rugged and reliable alternative to labor-intensive cable in conduit wiring methods 
    • For use on feeders and branch circuits for power distribution systems per NEC Articles 328 and 330 
    • For use in Class I, II and III, Divisions 1 and 2; and Class I, Zones 1 and 2 hazardous locations per NEC Articles 501, 502, 503 and 505 
    • Installed on metal racks, troughs, in raceways, in cable trays or secured to supports spaced not more than six feet apart 
    • Installed in both exposed and concealed work, wet or dry locations, directly buried or embedded in concrete 
    • Recognized for use on fixed or floating offshore petroleum facilities as recommended by the American Petroleum Institute 

    Features: 
    • CCW armor provides an impervious barrier to moisture, gas and liquids and meets grounding requirements of UL 1072 and the NEC 
    • Triple Extrusion: The strand shield, EPR insulation and insulation shield are all extruded in one operation 
    • General Cable’s EPR insulation system has outstanding corona resistance and high dielectric strength, and it provides electrical stability under stress 
    • Meets cold bend at -55°C 
    • 105°C continuous operating temperature, wet or dry 
    • 140°C emergency rating 
    • 250°C short circuit rating 

    Specifications: 
    Design Adherence: 
    • ICEA S-93-639/WC74, 5-46 kV Shielded Power Cables 
    • AEIC CS8 Specification for Shielded Power Cable, 5 – 46 kV 
    • UL 1072 Medium-Voltage Power Cables 
    • UL 1569 Metal Clad Cables 
    • UL 2225 Cables and Cable Fittings for Use in Hazardous Locations 
    • UL 1309 Marine Shipboard Cable 

    Flame Tests: 
    • ICEA T-29-520 (210,000 BTU/hr) 
    • IEEE 383 (70,000 BTU/hr) 
    • CSA FT4 
    • IEEE 1202 (70,000 BTU/hr) 
    • UL 1581 (70,000 BTU/hr) 
    • IEC 60332-3 Cat. A 

    Compliances: 
    • UL Type MV-105 or UL Type MC-HL, SUN RES, CT USE, DIR BUR, -40°C, FT4, UL File # E90501 
    • UL Listed Marine Shipboard, UL File # E85994 
    • CSA Type HL, SR, FT4, -40°C, CSA File # 27161 
    • American Bureau of Shipping (ABS) Listed for CWCMC

    cond. size
    (awg/
    kcmil)
    no.
    of
    cond.
    insulation
    thickness
    nominal o.d.
    over
    insulation
    bare
    ground
    (awg)
    nominal
    core o.d.
    nominal
    armor o.d.
    jacket
    thickness
    nominal
    overall o.d.
    approximate
    net weight
    ampacity
    general 
    cable part
    number
    mils mm inches inches inches mm mils mm inches mm lbs/
    1000ft
    kg/
    1000m
    in air¹
    direct
    burial²
    3/c with ground mc-hl or mv-105, 345 mils epr, 25 kv 133% and 35 kv 100% insulation level3
    1 (19/w)
    (42.4 mm²)
    3 345 8.8 1.04 4 2.48 2.89 73.4 75 1.91 3.05 77.5 4,100 6,101 210 225 9860.00103104
    1/0 (19/w)
    (53.5 mm²)
    3 345 8.8 1.07 4 2.56 2.98 75.7 75 1.91 3.14 79.8 4,500 6,697 240 255 9860.11003104
    2/0 (19/w)
    (67.4 mm²)
    3 345 8.8 1.11 4 2.65 3.11 79.0 85 2.16 3.30 83.8 4,950 7,366 275 290 9860.21003104
    4/0 (19/w)
    (107 mm²)
    3 345 8.8 1.22 3 2.88 3.41 86.6 85 2.16 3.60 91.4 6,200 9,227 360 345 9860.41003103
    250 (37/w)
    (127 mm²)
    3 345 8.8 1.27 3 2.97 3.63 92.2 85 2.16 3.81 96.8 6,800 10,119 400 410 9860.25003102
    350 (37/w)
    (177 mm²)
    3 345 8.8 1.36 2 3.20 3.76 95.5 85 2.16 3.94 100.1 8,000 11,905 490 495 9860.35003102
    500 (37/w)
    (253 mm²)
    3 345 8.8 1.48 1 3.45 4.10 104.1 85 2.16 4.23 107.4 10,150 15,105 600 590 9860.50003101